Type Selection Table:
Torque Running Time Power Supply Auxiliary Switch Model/Type
4 Nm <50s 24VAC/DC None DA4MU24-D
4 Nm <50s 24VAC/DC 1-SPDT DA4MU24-DS
6 Nm <70s 24VAC/DC None DA4MU24-D
6 Nm <70s 24VAC/DC 1-SPDT DA4MU24-DS

Technical parameter
    DA2MU24-D/DS DA2MU24-D/DS
Electrical data Nominal voltage AC24V 50/60Hz DC24V AC24V 50/60Hz DC24V
Electrical data Nominal voltage range AC/DC 19.2…28.8V AC/DC 19.2…28.8V
Electrical data Power consumption 3W@Nominaltoque/0.5W@holding 3W@Nominaltoque/0.5W@holding
Electrical data Wire sizing 0.5m㎡ 0.5m㎡
Function data Torque 4Nm 4Nm
Function data Damper size 0.8㎡ 1.2㎡
Function data Direction of rotation Manual regulation Manual regulation
Function data Manual override
Gearing latch disengaged by push button,
self-resetting
Gearing latch disengaged by push button,
self-resetting
Function data Angle of rotation Max90° Max90°
Function data Running time <50S(90°) <70S(90°)
Function data Sound power level 45dB 45dB
Function data Position indication Mechanical Mechanical
Working conditions Protection class Ⅲ (safety low voltage) Ⅲ (safety low voltage)
Working conditions Protection level IP44 IP44
Working conditions Ambient temperature -20…+50℃ /IEC 721-3-3 -20…+50℃ /IEC 721-3-3
Working conditions Inventory temperature -30…+80℃ /IEC 721-3-2 -30…+80℃ /IEC 721-3-2
Working conditions Humidity test 95%RH,non condensing(EN60730-1) 95%RH,non condensing(EN60730-1)
Weight Dimensions Dimensions(L×W×H) See "Dimensions" See "Dimensions"
Weight Dimensions Shaft length > 50mm > 50mm
Weight Dimensions Weight < 0.75kg < 0.75kg

For operation of air control dampers in HVAC system.
Torque: 4Nm/6Nm
Nominal voltage: AC/DC 24V, AC100…240V
Control: ON/OFF, 2/3-Point
-DS type include 2 auxiliary switch.