Long Descriptions
2Nm ON/OFF General Damper Actuator
Torque | Running Time | Power Supply | Auxiliary Switch | Model/Type |
2 Nm | <30s | 24VAC/DC | None | DA2MU24-D |
2 Nm | <30s | 24VAC/DC | 1-SPDT | DA2MU24-DS |
DA2MU24-D/DS | ||
Electrical data | Nominal voltage | AC24V 50/60Hz DC24V |
Electrical data | Nominal voltage range | AC/DC 19.2…28.8V |
Electrical data | Power consumption | 3W@Nominaltoque/0.5W@holding |
Electrical data | Wire sizing | 0.5m㎡ |
Function data | Torque | 2Nm |
Function data | Damper size | 0.5㎡ |
Function data | Direction of rotation | Manual regulation |
Function data | Manual override | Gearing latch disengaged by push button, self-resetting |
Function data | Angle of rotation | Max90° |
Function data | Running time | <30S(90°) |
Function data | Sound power level | 45dB |
Function data | Position indication | Mechanical |
Working conditions | Protection class | Ⅲ (safety low voltage) |
Working conditions | Protection level | IP54 |
Working conditions | Ambient temperature | 20…+50℃ /IEC 721-3-3 |
Working conditions | Inventory temperature | -30…+80℃ /IEC 721-3-2 |
Working conditions | Humidity test | 95%RH,non condensing(EN60730-1) |
Weight Dimensions | Dimensions(L×W×H) | See "Dimensions" |
Weight Dimensions | Shaft length | > 50mm |
Weight Dimensions | Weight | < 0.5kg |
For operation of air control dampers in HVAC system.
Torque: 2Nm
Nominal voltage: AC/DC 24V, AC100…240V
Control: ON/OFF, 2/3-Point
-DS type include 1 auxiliary switch.
|